Description
Specifications
Overview
Model Designation PHI-HB-INV-6kW
Environmental Protection IP65
Protective Class I
Battery Input Data
Nominal Battery Voltage 48VDC
DC Voltage Range 40~62VDC
Maximum Charging Voltage 62VDC (Configurable)
Maximum Charging Current 100 A
Maximum Discharging Current 150 A
Charging Curve 3 Stages / Float
Charging Strategy for Li-Ion Battery Self-adaption to BMS
Number of DC Connections 1
PV String Input Data
Maximum DC Input Power 7,500 W
Nominal DC Voltage 360VDC
Maximum DC Input Voltage 600VDC
MPPT Range 120~550VDC
Start-up Voltage / Initial Feed In Voltage 125VDC / 160VDC
Maximum Input Current per MPPT 15 A
Maximum Isc PV 21 A
Maximum Inverter Back Feed Current to Array 0 A
Number of MPP Trackers 2 with 2 inputs each
AC Output Data (On-grid)
Nominal Apparent Power Output to Utility Grid 6,000 VA
Nominal Output Voltage 220VAC / 240VAC L1-L2, 110VAC / 120VAC L-N
Nominal Output Frequency 50 / 60 Hz
Output Frequency Range 47.5~51.5 Hz or 59.3~60.5 Hz
Output Voltage Range 105.5–132VAC per phase
Inrush Current/Duration 30 A per phase / 20 ms
O/P DC Component <100 mA
Output Power Factor >0.99 (Adjustable from 0.9 leading to 0.9 lagging)
Output THDi (@Nominal Output) <3%
Switch Over Time (Grid Down) <8 ms
AC Output Data (Back-up)
Maximum Output Apparent Power 6,000VA
Instantaneous Power (100ms) 12,000VA
Surge Power (5 sec) 9,000VA
Maximum Output Active Power 6,000 W
Nominal Output Voltage 220VAC / 240VAC L1-L2, 110VAC / 120VAC L-N
Nominal Output Frequency – Auto Sensing 50/60 (±0.1 Hz)
Output THDv (@Linear Load) <3%
Output THDv (@PF 0.8 Non-Linear Load) <5%
Parallel Function Yes
Parallel Units 9
Automated Generator Start Included
Efficiency
Maximum Solar to Utility Efficiency 96.50%
Maximum Battery to Load Efficiency 91.00%
Protection
Anti-Islanding Protection Integrated
PV String Input Reverse Polarity Protection Integrated
AFCI (Arc-Fault) Integrated
Ground Fault Monitoring Integrated
Insulation Resistor Detection Integrated
Residual Current Monitoring Unit Integrated
Output Over Current Protection Integrated – 90 A per phase
Output Short Protection Integrated
Rapid Shut Down Relay Integrated
General Data
Operating Temperature Range -13 – 140 °F (-25 – 60 °C)
Transformerless Yes
Consumption Modes UPS, Self-Consumption, TOU, Off- Grid Backup, Grid-Tied without Batteries
Relative Humidity 0~90%
Operating Altitude <13,123 ft (4,000 m)
Cooling External Force Convection
Noise <50 dB
Dimensions (W x H x D) 20.28 x 27.55 x 8.5 in (515 x 700 x 215.5 mm)
Noise <50 dB
Dimensions (W x H x D) 20.28 x 27.55 x 8.5 in (515 x 700 x 215.5 mm)
Communications Interface
User Interface LCD / Phone Application (iOS & Android)
Communication with BMS CANBUS
Communications Between Inverters CANBUS
Communication with Cloud – API with Grid Services via EnergyTrakTM Gateway
Communication Port RS-232
Intelligent Slot RS232 / USB, BMS, Wi-Fi
Certifications / Standards
Grid Regulation UL 1741SA-2020, UL 1741 SB-2020 (in process), IEEE1547.1-2020
Safety Regulation 6-1, 6-4 IEC / EN 62109-1&2
EMC EN 61000-6-2, EN 61000-6-3
Reviews
There are no reviews yet.